Weight Transmitter UWT 6008

UWT 6008

The UWT 6008 weight transmitter comes from the Pavone Systems experience. It is a unique product in the weight transmitter family and is ideal for all industrial applications where it is necessary to know the load distribution on the different cells. It is able to monitor all load cells and generate alarms due to excessive cell signal drift, missing connections, failure of one of the cells, unbalanced weight distribution. The emulative control allows the continuity of work of the weighing system even in case of failure on one of the load cells, up to the replacement of the same. The Software Optimation is given for free. This Software allows you to run certain activities such as calibration or monitoring directly from your computer. The Optimation software is provided by Pavone Systems and guarantees a perfect instrument run. PWS: 43/2018

Further Information

Technical Specifications in PDF

Watch our tutorial

Product code: PSDA6000

Technical Specifications

Measuring range: -3.9 ÷ +3.9 mV/V
Input sensitivity: 0.02 µV/count
Full scale non-Linearity: <0.01%
Gain drift: < 0.001% FS/°C
Display: 128 x 64-pixel graphic LCD
A/D Converter: 24 bits
Internal Resolution: > 16.000.000 points
Trasducer input voltage: 5 Vdc (max. 230 mA)
Frequency signal acquisition: 12.5 ÷ 300 Hz
Visible resolution (in divisions): 999999
Divisions value (adjustable): x1, x2, x5, x10, x20, x50
Decimal figures range: 0 ÷ 4
Temperature range: -10 ÷ + 50°C (humidity max 85% no condensation)
Storage temperature: -20 ÷ +70°C
Filter: 5 ÷ 250 Hz
Logic output: 2 relays, Max. 48 Vac/Vdc, 2A each
Logic input: 2 opto-isolated at 12/24 Vdc PNP (external power supply)
Serial port: 1 USB device + 1 RS232C + 1 RS485, Fieldbus, ASCII or Modbus RTU
Analog output Non-Linearity: < 0,02%
Temperature drift analog output: 0,001% FS/°C
Power supply: 12-24 Vdc ±15% - Power consumption 4 W
Microcontroller: ARM Cortex M0+ at 32 bits, 256KB Flash reprogrammable on-board from USB
Data storage: 64 Kbytes expandable up to 1024 Kbytes
Regulatory compliance: EN61000-6-2, EN61000-6-3 for EMC; EN61010-1 for Electrical Safety, EN45501 for metrology
Number of load cells: 1 ÷ 8
Dimensions: 100 x 75 x 110 mm (L x H x P)

Related products

Tutorial 1 / 2

Tutorial 2 / 2